Features and Applications
General Characteristics for GX-Series Subgrouping Cables
Standards List
Specifications - Riser | Plenum


Features and Applications

  • Tight-buffered multifiber cable design allows subcables to be routed to multiple locations such as in wiring racks or wiring closets
  • Core-LockedT outer jacket surrounds the subcables for excellent crush resistance, survivability, and use in long vertical installations
  • Multifiber color-coded subcables, each similar to the DX-Series Distribution Cable
  • Best design for multimode and single-mode fiber hybrid/composite cables (See part number note on page 24.)
  • Color-coded subcables are easy to identify for improved cable management in routing and termination
  • Helically stranded cable core for flexibility, survival in difficult pulls, and mechanical protection for the optical fibers
  • Cable ideal for direct pulling with wire mesh grips
  • High performance tight-buffered coating on each optical fiber for environmental and mechanical protection
  • Suitable for both indoor and outdoor use -- no need to splice outdoor cable to indoor cable at the building entrance
  • Flame-retardant for indoor installations
  • Fungus-resistant, water-resistant, and UV-resistant for outdoor use
  • Subgroup cables of GX-Series plenum cables are individually Plenum-rated and can be UL Plenum labeled
  • 12 to 288 fibers in various subgroup cable sizes; higher fiber counts available upon request
  • Water-blocked G-Series and GX-Series Subgrouping Cables are available

General Characteristics for GX-Series Subgrouping Cables

  Riser Plenum
Minimum Bend Radius:    
Under Installation Tensile Load 15X outside diameter 15X outside diameter
Under Long-Term Tensile Load 10X outside diameter 15X outside diameter
Operating Temperature -40°C to +85°C -40°C to +85°C
Storage Temperature -55°C to +85°C -40°C to +85°C
Crush Resistance 2,100 N/cm 2,100 N/cm
Impact Resistance 1,500 impacts 1,500 impacts
Flex Resistance 2,000 cycles 2,000 cycles
These specifications are subject to change without prior notification.

Standards List

Optical Cable Corporation's indoor/outdoor tight-buffered fiber optic cables meet the functional requirements of the following standards:

  • ANSI X3T9.5 PMD
  • ATM 155 Mb/s
  • FDDI 100 Mb/s
  • Fibre Channel FC-PH
  • GR-409-CORE
  • ICEA-S-83-596
  • TIA-568
  • TIA-598-B
  • TIA-758 (water-blocked cables)

UL-listed type OFNP in accordance with NEC sections 770-179 (A) and 770-154 (A) for use in ducts, plenums, and air-handling spaces. Meets or exceeds requirements for intra-building fiber optic cables as outlined in GR-409-CORE.